ACH550-UH User’s Manual
1-57
Application macros
Pump Alternation macro
This macro configures for pump alternation applications, usually used in booster
stations. To adjust/maintain pressure in the network, the speed of the one pump
changes according to a signal received from a pressure transducer. When the
variable speed pump reaches a maximum speed limit, auxiliary pumps start as
needed. When using process PID, see
on page
. To use
more than one (the default) Auxiliary pump, see parameter group 81.
Parameters Changed Relative to HVAC Default
Parameter
Value
Parameter
Value
9902
APPLIC
MACRO
7 (
PUMP
ALTERNA
)
2203
DECELER
TIME
1
10.0 s
1201
CONST
SPEED
SEL
0 (
NOT
SEL
)
8109
START
FREQ
1
58.0
HZ
1401
RELAY
OUTPUT
1
31 (
PFA
)
8110
START
FREQ
2
58.0
HZ
1608
START
ENABLE
1
0 (
NOT
SEL
)
8111
START
FREQ
3
58.0
HZ
2101
START
FUNCTION
8 (
RAMP
)
8123
PFA
ENABLE
1 (
ACTIVE
)
2202
ACCELER
TIME
1
10.0 s
1 SCR
2 AI1
3 AGND
4 10V
5 AI2
6 AGND
7 AO1
8 AO2
9 AGND
10 24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
X1
+
mA
mA
External reference
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Start/Stop:
Activate to start drive
Not configured
Not configured
PFA interlock 1:
Deactivate to stop drive (P 8120)
Not configured
Relay output 1 (P 1401)
Default operation:
PFA
(starts lag pump)
Relay output 2 (P 1402)
Default operation:
Running
=>22 connected to 24
Relay output 3 (P 1403)
Default operation:
Fault (-1)
=>25 connected to 27
Output current:
0(4)…20 mA
Not configured
Analog input circuit common
PID feedback:
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
(Fault => 25 connected to 26)
+
J1
AI1: 0(4)
…
20 mA
AI2: 0(4)
…
20 mA
ON
J1 Jumper Settings
ON
ON
12
J1
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......