*Set test current
0 8.8A 23V
Motor voltage is increased until motor current
fl
ows.
Calibration is performed.
Stop inspection !
Release inspection run push-button
*Result: 2.7A
132-222 -> 176/ 356
ENC_ABS=263
ENC_OFF=356 [END]
Result of the adjustment is displayed (176 / 356)
If ENC_OFF = ? is displayed, it is not possible to determine the correct
Encoder Offset. In this case one of the two results (176 or 356 in the
example) is correct. It is recommended to move the motor shaft to a different
position by brie
fl
y releasing the brake and to repeat the calibration. If correct
calibration i still not possible, a test run must be made with both of the
received results. With one result the motor runs error-free, with the other
result uncontrolled movements of the motor can occur!
Save new ENC_OFF?
[no] [yes]
Prompt whether determined Encoder-Offset (ENC_OFF) is to be saved in
the
Encoder Calibration/ENC_OFF
menu
[yes]:
Value is saved
[no]:
Value is not saved
Original operating instructions
ZETADYN 3C
Special functions
R-TBA08_03-GB 1619
Part.-No. 00163322-GB