15.10
Controlled emergency stop in inclined elevators
If an emergency stop is implemented in inclined elevators by suddenly closing the brakes, the abrupt
stop can lead to injury to passengers. To avoide this, the cabin should also be braked controlled in
emergency stop.
The
/DELAY
input function is available for this.
When deactivating the input with the
/DELAY
function, the motor is delayed with the delay para-
meterised in the
Controller/A_MAX
menu (see
fi
g.).
Information
At the end of the emergency stop the fault
E208 - DELAY active
is output.
A new run can only be performed after activating the
/DELAY
input function!
RF
V1
V3
RV1/RV2
/DELAY
RB
MB
X-IN
X-OUT
V
t
Controlled emergency stop
RF
Controller enable
V1
Positioning speed
V3
Travel Speed
RV1 / RV2
Direction default
/DELAY
Delay in emergency stop
RB
Controller ready
MB_Brake
Mechanical brake