Parameter
Function
Explanation
35:HY_DOWN
Direction DOWN at hydraulic elevator
with Bucher aggregate type Saturn
ALPHA and Orion ALPHA
The input functions RF+RV2+V1 are activated simultaneously
when the input is activated
only in ZETADYN 3xx-HY
36:/DELAY
Delay in emergency stop
When deactivating the input the motor is braked with the delay
set in the "Controller/A_MAX" menu
37:DTE
ZIEHL-ABEGG test function
Reserved for ZIEHL-ABEGG
38:RECORD
Recorder function
Start or stop measurement by external signal
Input activated:
Measurement is active
Input deactivated:
Measurement is stopped and saved
39:INV_A1
Direction UP at hydraulic elevator with
Bucher aggregate type Orion ALPHA
Inverting the analog target value A1
40:FKT.ana
ZIEHL-ABEGG test function
Reserved for ZIEHL-ABEGG
41:Monitor
Monitoring function for manually evac-
uation
Shown evacuation direction and evacution speed
42: LZ
Distance-dependent deceleration after
standstill
With active input there is a deceleration after speed 0, even
when travel speeds are activated.
The deceleration from travel speed V1 depends on the distance
programmed for the parameter S_10.
43:STANDBY1
Standby 1
Switching the ZETADYN 3C to Standby 1 function to save en-
ergy
44: ZR_RDY
ZArec ready
ZArec monitoring function
Parameter descriptions for digital outputs
Parameter
Function
Explanation
Off
Output has no function
Output is open all the time
MotContact
Controller ready
Switching the motor contactors
Contact closes when the following signals are applied: Controller
enable, traveling speed and direction default. When the contact
closes, the motor contactors must be switched immediately.
RB_Invers
Inverted function of "RB contactor"
Contact opens when the following signals are applied: Controller
enable, traveling speed and direction default.
V<V_G1
Speed monitoring
Contact opens when the tolerance set in the "Control system"
menu V_G1 is exceeded.
V<V_G2
Speed monitoring
Contact opens when the tolerance set in the "Control system"
menu V_G2 is exceeded.
V<1.1*V_3
Speed monitoring
Contact opens when the traveling speed V3 is exceeded by
10%.
Warning
Warning
Monitoring of the motor temperature and the temperature of the
power section.
Contact opens if a malfunction advance warning is present
because of an excess temperatur. The current trip will be trav-
eled to the end. The advance warning can be evaluated by the
open loop control and a new start can be prevented.
Err
Err
Contact is closed if no error is present in the frequency inverter.
EVAC.DIR
Evacuation direction
Contact open: Car is lighter than counterweight
Contact closed: car is heavier than counterweight
MB_Brake
Mechanical brake
Contact closes after expiration of the magnetic
fl
ux creation
time. When the contact close, the mechanical brake must be
immediately opened via an external contactor.
INV V<V_G1
inverted function of "V<V_G1
Contact closes when the limit value set in the "Control system"
menu V_G1 is exceeded.
INV V<V_G2
inverted function of "V<V_G2
Contact closes when the limit value set in the "Control system"
menu V_G2 is exceeded.
V=0
Speed = 0
Contact opens at start of travel, when actual speed > 0 m/s
Contact closes at the end of travel when actual speed = 0 m/s
and output for control mode contactor = 0
PFU
Recuperation unit
Switching the feedback unit to standby function to save energy
Original operating instructions