The following information is displayed when the error list is opened and the key is pressed
additionally:
? B R : F a h r t - F e h l e r ?
E 5 8 3 S 4 3 0 - 1 . 6 h
0 0 0 0 0 0 1 x x x 2 8 C
S : C h e c k M O P - s t a t u s
1
2
4
5
6
7
8
3
1
Error description
2
Error no.
3
Operation condition (S=status)
4
Indication how many trips ago the error occurred
5
Status in which the error occurred is in plain text
6
Time how long ago the error occurred
7
Temperture power stage
8
Additional information (option)
Scroll through fault list:
the fault list can be scrolled through using the two arrow keys.
Scroll up (reduce fault serial number)
Scroll down (increase fault serial number)
Determine time of fault
When i key is pressed, the difference from the current number of
travels and operting time is displayed
"
BC:Alarm/fault
3
E912 S422 -2.4h
-0000189 12C
"
01 RV1 0.00m +12A
In CANopen lift and DCP operation the time at which the error occurred is saved and displayed in the
error list.
? B R : F a h r t - F e h l e r ?
E 5 8 3 S 4 3 0 1 0 : 3 0
0 0 0 0 0 7 6 x x x 2 8 C
?
0 0
R V 1 5 . 9 1 m + 1 2 A
1
1
Time at which the error occurred
13.4
Delete error memory
The fault memory is wiped by means of an entry in the
Statistic/ST_CLR=ON
.
The following parameters are reset:
•
ST_LST (Error list)
•
ST_RES (Number of interruptions in the mains supply)
•
ST_SRF (Number of trip interruptions due to an interruption in the control enabling)
•
ST_SCO (Number of trip interruptions due to an interruption in the contactor monitor)
Original operating instructions
ZETADYN 3C
Error diagnosis
R-TBA08_03-GB 1619
Part.-No. 00163322-GB
134/204