Table 78: Setpoints
Button
Access level Description
Econ
Temperature
Control Max
Loading
Delta
Admin
Range 0.1 to 100.0, Default 1.0
Displays the maximum temperature difference used to initiate
changes in the economizer mode.
Econ
Temperature
Control Max
Unloading
Delta
Admin
Range 0.1 to 100.0, Default 1.0
Econ
Temperature
Control Kp
Admin
Range 0.1 to 15.0, Default 5.0
Adjusts the Proportional Gain.
Econ
Temperature
Control Ti
Admin
Range 0.1 to 200.0, Default 25.0
Adjusts the Integral Gain.
Econ
Temperature
Control Td
Admin
Range 0.0 to 200.0, Default 0.0
Adjusts the Derivative Gain.
Econ PRV
Output Gain Admin
Range 0.1 to 10.0, Default 1.0
Displays the output gain used to control the economizer Pre-
Rotation Vanes.
Table 79: Programmable
Button
Access level Description
Change
Setpoints
Service or
Admin
Pressing this button will display a green box around the first
programmable item on the screen. The arrow keys can be used to
move the box around to select the item to program.
Default
Setpoints
Service
Pressing this button will display a dialog box telling the user to
“Press Enter to set all Econ Capacity Control Setpoints to their
default value. Press Cancel to leave setpoints unchanged.” If the
user presses Enter, all Econ Capacity Control Setpoints will return to
the default settings.
Table 80: Navigation
Button
Access level Description
Home
View
Returns the user to the HOME Screen.
Capacity
Control
Service
Allows the user to navigate to the Economizer Capacity Control
Screen.
Anti-Surge
Tuning
Service
Allows the user to navigate to the Econ Anti-Surge Tuning Screen.
YK-EP Style B Centrifugal Chiller
90
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...