7. Cycling Shutdown Contacts
The chiller operating program resides in the OptiView Control Center Microboard. The Control
Center could be equipped with the following Microboards:
•
031-02430-001 – Shipped in new production chillers after June 2006. This is an upgraded
version of the 031-02430 microboard. The upgrade is necessary to operate with the Medium
Voltage Solid State Starter, Medium Voltage Variable Speed Drive and those Variable Speed
Drives and Style B Solid State Starters that serially communicate with the microboard using
Modbus Protocol.
The upgrade includes a larger BRAM (U38) and an additional RS-485 port on COM2 serial port for
Modbus communications.
Software version (D.Exx.01.xx.yzz) are alphanumeric codes that represent the application, language
package and revision levels per below. Each time the controls portion or language section is
revised, the respective revision level increments.
•
D – Industrial chiller
•
Exx – Used on Microboard 031-02430-001
•
01 – YKEP chiller
•
xx – controls revision level (00, 01, etc)
•
y – language package (0 equals English only, 1 equals NEMA, 2 equals CE, 3 equals NEMA/CE )
•
zz – language package revision level (00, 01, etc)
•
031-03630-001 – Shipped in new production chillers after August 2016. This is an upgraded
microboard that operates with the Electro-Mechanical, Medium Voltage Solid State Starter,
Medium Voltage Variable Speed Drive and those Variable Speed Drives and Style B Solid State
Starters that serially communicate with the microboard using the Modbus Protocol.
Software version (Z.OPT.01.xx.yzz) are alphanumeric codes that represent the application, language
package and revision levels per below. Each time the controls portion or language section is
revised, the respective revision level increments.
•
Z – Industrial chiller
•
OPT – Used on Microboard 031-03630-001
•
01 – YKEP chiller
•
xx – controls revision level (00, 01, etc)
•
y – language package (0 equals English only, 1 equals NEMA, 2 equals CE, 3 equals NEMA/CE )
•
zz – language package revision level (00, 01, etc)
15
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...