Table 190: Programmable
Button
Access level Description
Secondary
Trigger
Operator
Selects the second parameter to be evaluated. Selection is made
from the Slot Numbers listing on the TREND COMMON SLOTS
Screen or the Master Slot Numbers List in this manual. Setting this
Slot Number to zero disables the Secondary Trigger.
Secondary
Operator
Operator
Selects the comparator for the Secondary Trigger’s relationship
to the Secondary Test. If the Secondary trigger is an Analog value,
selections are: <, <=, =, =>, >. If the Secondary Trigger is a digital
event, selections are: Equal To, Not Equal To.
Secondary
Test
Operator
Selects the value or condition that the Secondary Trigger is
compared to. Selection ranges from the Secondary Trigger
minimum to the Secondary Trigger maximum.
Table 191: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
Trend Setup
–
Returns user to TREND SETUP Screen.
183
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...