Table 24: Programmable
Button
Access level Description
Set
Service
Pressing this button will open a dialog box where the user can
manually enter a valve command. Once a legitimate value has
been entered and the Enter key pressed, the Condenser Level
Control Valve Mode will be set to Manual if it had been in Auto. The
Condenser Level Control Valve Command will be set to the entered
value.
High
Threshold
Admin
Sets the high limit for the Subcooler Effectiveness Warning.
(Adjustable 0 to 100%; default 50%).
Low
Threshold
Admin
Sets the low limit for the Subcooler Effectiveness Warning.
(Adjustable 0 to 100%; default 50%).
KP
Admin
Sets the Proportional value of the PID control loop. (Adjustable 0.1
to 15; default 1.0).
Ti
Admin
Sets the Integral value of the PID control loop. (Adjustable 0.1 to
200; default 100).
Td
Admin
Sets the Derivative value of the PID control loop. (Adjustable 0.0 to
200; default 0.0).
Table 25: Navigation
Button
Access level Description
Home
View
Returns user to HOME Screen.
Condenser
View
Returns user to CONDENSER Screen.
41
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...