Table 59: Display only
Field/LED name
Description
Stall Count
Displays the number of times that the system had detected an
Economizer Compressor Stall.
Stall Time
Displays the accumulated time that the Stall Detector Board output
is greater than the High Limit Setpoint voltage while the chiller is
running.
VGD Control State
Shows the current state of the VGD Control. It will show various
messages as follows:
•
Undefined
•
Disabled
•
Stall Waiting
•
Probing
•
Stall Reacting
•
PRV Override
•
Sensor Failure Override
•
Extreme Stall Override
•
Manual Hold
•
Manual Open
•
Manual Close
•
Inactive
Table 60: Programmable
Button
Access level Description
Extreme Stall
Duration
Service
(10 to 20 minutes; default 10 minutes.)
The Extreme Duration override occurs when the Variable Geometry
Diffuser (VGD) stall voltage is two times higher than the high limit
for longer than 10 minutes. At this time, the VGD will be opened and
a warning message displayed. The VGD will remain open until the
warning is manually cleared by the operator. Once cleared, the VGD
Control will return to normal operation.
PRV VGD
Inhibit
Service
(40 to 100%, Default 95%)
If PRV position is greater than the PRV VGD Inhibit (95%), the VGD
will open in pulse mode just the same way as in the Probing state.
PRV Offset
Service
(0 to 5%, Default 3%)
When VGD control enters the Wait State, the PRV position is PRV
wait Start position. During the Wait state, if PRV position is greater
than the PRV wait Start + 3%, the VGD control will enter the Probing
state.
YK-EP Style B Centrifugal Chiller
72
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...