Table 134: Display only - Motor bearings
Field/LED name
Description
High Vibration Shutdown
Displays the High Vibration safety shutdown threshold for the Shaft
End and Opposite Shaft End bearings. Not shown when the Motor
Vibration Protection Setpoint on MOTOR DETAILS Screen is set to
Disabled. The threshold used for this setpoint will either be the
values entered by the Vibration Setup Setpoint or values derived
from the Vibration Baseline Setpoints (refer to
Vibration Setup
in Table 135). Also displayed is the Delay, which is the amount of
time the vibration must exceed the shutdown threshold before the
shutdown occurs.
High Vibration Warning
Displays the High Vibration Warning threshold for the Shaft End and
Opposite Shaft End bearings. Not shown when the Motor Vibration
Protection Setpoint on MOTOR DETAILS Screen is set to Disabled.
The threshold used for this setpoint will either be the values entered
by the Vibration Setup Setpoint or values derived from the Vibration
Baseline Setpoints (refer to
Vibration Setup
displayed is the Delay, which is the amount of time the vibration
must exceed the warning threshold before the warning is displayed.
Vibration Input Gain
Displays the Vibration Input Gain value, as programmed with the
VIBRATION GAIN Setpoint key. Not shown when the Motor Vibration
Protection Setpoint on MOTOR DETAILS Screen is set to Disabled.
High Bearing Temperature
Shutdown
Displays the High Bearing Temperature safety shutdown threshold,
as programmed with the BEARING SETUP Setpoint key. Not shown
when Bearing Temperature Protection Setpoint on MOTOR DETAILS
Screen is set to Disabled.
High Bearing Temperature
Warning
Displays the High Bearing Temperature warning threshold, as
programmed with the BEARING SETUP Setpoint key. Not shown
when Bearing Temperature Protection Setpoint on MOTOR DETAILS
Screen is set to Disabled.
137
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...