![York YK-EP Operation And Maintenance Manual Download Page 88](http://html1.mh-extra.com/html/york/yk-ep/yk-ep_operation-and-maintenance-manual_4221207088.webp)
Economizer capacity control setpoints screen
Figure 30: Economizer capacity control setpoints screen
This screen displays a view of the economizer capacity control setpoints and buttons. Service Level
Access is required to navigate to this screen.
Table 77: Adjustable
Field/LED
name
Access level Description
High
Head for
Refrigerant
Flow
Service
Range 5 to 150 PSID, Default 64 PSID
This displays the high head setpoints at which the economizer
will activate. These points can be changed according to when the
operator wishes the economizer to start operating.
Refrigerant
Flow Criteria
at High Head
Service
Range 100 to 50000 CFM, Default 6000 CFM
Displays the refrigerant flow in CFM that is where the economizer
will activate in the high head condition.
Low Head for
Refrigerant
Flow
Service
Range 5 to 150 PSID, Default 30 PSID
This displays the low head setpoints at which the economizer
will activate. These points can be changed according to when the
operator wishes the economizer to stop operating.
Refrigerant
Flow Criteria
at Low Head
Service
Range 100 to 50000 CFM, Default 8200 CFM
Displays the refrigerant flow in CFM that is where the economizer
will activate in the low head condition.
YK-EP Style B Centrifugal Chiller
88
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...