the total RMS value of all the harmonic current supplied by the main power to the VSD divided by
the chiller Full Load Amps, in percent. A standard VSD, less the optional filter typically has an input
current TDD level on the order of 28-30%. The chiller can be started after the Operator presses the
WARNING RESET button.
VSD – Low Frequency Detected
After a 20 second bypass after entering System Run, if the VSD frequency decreases to below 1 Hz
less than the minimum allowed frequency for 25 continuous seconds, this shutdown is initiated.
The minimum allowed frequency for the VSD is 25 Hz for 50 Hz units; 30 Hz for 60 Hz units. The
Operator must press the WARNING RESET button to reset the fault.
219
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...