History screen
Figure 59: History screen
This screen allows the user to browse through the faults. In order to get a more thorough reporting
of the system conditions at the time of the recorded shutdown, move to the subscreen HISTORY
DETAILS.
The user may use the SELECT FAULT button to select the history to view. At this point the VIEW
DETAILS button is used to jump to a subscreen containing stored chiller parameters values at the
time of the shutdown. Additionally, the PRINT HISTORY button can be used to generate a hard-copy
report of the parameter values at the time of the shutdown.
Table 167: Display only
Field/LED name
Description
Last Normal Shutdown
This window displays the date and time and the description of the
last normal shutdown. A normal shutdown is defined as:
•
Local (Soft Stop Switch)
•
Remote (Digital, Analog or ISN (BAS))
Last Fault While Running
This window displays the date and time and the description of the
last safety or cycling shutdown while the system was running.
Last 50 Faults
This window displays a chronological listing (most recent first) of
the date and time and the description of the last 50 safety or cycling
shutdowns that occur while the system is running or stopped.
YK-EP Style B Centrifugal Chiller
166
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...