Table 141: Programmable
Button
Access level Description
PRV Position Service
This setpoint allows the software to be used in all YK-EP chillers,
whether equipped with the potentiometer or not. The PRV position
will be shown on respective screens when Enabled.
•
Enabled – Automatically set to this setting if Hot Gas Bypass
or Variable Geometry Diffuser (VGD) is enabled on the
OPERATIONS Screen or Motor Drive Type Setpoint is set to
VSD or MVVSD. It is connected to the Microboard J7.
•
Disabled – Set to this position when not equipped with a PRV
potentiometer. If equipped with a VSD, MVVSD or the Hot Gas
Bypass, or Variable Geometry Diffuser is enabled; this setpoint
is automatically enabled and cannot be set to disabled.
Motor Drive
Type
Service
Allows a Service Technician to enter the applied compressor motor
type as either Electro-Mechanical (EM), Solid State Starter (SSS-Mod
A), Solid State starter (SSS – Mod B), Variable Speed Drive-60 Hz
Variable Speed Drive-50 Hz, MVVSD or MVSSS.
Anti-Recycle Service
Allows a Service Technician to enable or disable the anti-recycle
timer for test purposes only.
Head
Pressure
Control
Service
Allows the Service Technician to enable or disable the Head Pressure
Control feature.
Heat
Recovery
Service
Allows the Service Technician to enable or disable the Heat Recovery
feature.
Power Failure
Restart
Operator
Allows the user to select Manual or Automatic restart after power
failure.
Coastdown
Service
Allows a Service Technician to select either Standard (electric
motor) or Enhanced (15 minutes–Steam Turbine applications).
When Standard is selected, the duration is programmable using the
Coastdown Time Setpoint between 240 and 900 seconds.
Motor
Monitoring
Service
Allows the Service Technician to enable or disable the Motor
Monitoring feature.
Pre-Run
Service
Allows Service Technician to select either Standard (30 seconds) or
Extended (180 seconds).
Oil Pump
Package
Service
Allows Service Technician to enter the applied oil pump drive type as
either Variable Speed or Fixed Speed.
YK-EP
Control
Service
Allows selection of YK-EP program functions.
Line
Frequency
Service
Sets the Line Frequency to either 60 Hz or 50 Hz as appropriate.
Motor Heater Service
Set to Enabled if motor heaters installed else, set to Disabled.
YK-EP Style B Centrifugal Chiller
146
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...