Table 69: Display only fields
Field/LED name
Description
Output frequency rating
This is the rated output frequency communicated by the MVVSD. This value is the
maximum drive frequency (Hz) when the MVVSD receives a 100% speed command
from the OptiView Control Center. If the value received is not 50 Hz or 60 Hz, INVALID
is displayed. If this is the case, then the Motor Voltage Rating (above) determines the
maximum frequency as follows:
•
Motor Voltage Rating: 2300 V, 3300 V, or 4160 V
•
Output Frequency Rating: 60 Hz or 50 Hz
Full Load Amps
Displays the maximum amps at which the motor can operate.
VSD cooling fans output (LED)
Lights when the digital output from the MVVSD control has set the Cooling Fans to
RUN.
Precharge relay output (LED)
Lights when the digital output from the MVVSD control has set the Precharge Relay to
ON.
Programmable
None
Table 70: Navigation
Button
Access level
Description
Home
View
Returns to the Home screen.
Motor
View
Displays the subscreen that provides more information about the motor.
Motor details
View
Displays the subscreen that provides information and setpoints pertinent to the Motor
Monitoring feature.
81
Model YD Mod D with OptiView Control Center
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...