Start inhibit messages
Table 139: Start inhibit messages
Message
Description
Discharge Valve #1 -
Open
The chiller (both compressors) is inhibited from starting because compressor #1 discharge
valve is not closed. This start inhibit is released when the valve has fully closed.
Discharge Valve #2 -
Open
The chiller (both compressors) is inhibited from starting because compressor #2 discharge
valve is not closed. This start inhibit is released when the valve has fully closed.
Motor #1 – Anti-recycle
The chiller (both compressors) is inhibited from starting because compressor #1 motor is
in the 30 minute anti-recycle period and compressor #2 is unable to run. This start inhibit is
released when the 30 minute timer expires.
Motor #2 – Anti-recycle
The chiller (both compressors) is inhibited from starting because compressor #2 motor is
in the 30 minute anti-recycle period and compressor #1 is unable to run. This start inhibit is
released when the 30 minute timer expires.
Motor #1 – Current >15%
FLA
The chiller (both compressors) is inhibited from starting because a motor current of >15%
FLA was detected on compressor #1 while it was not running. This inhibit is set instantly with
no delay and the oil pump is started as soon as the motor current is detected. The starting
frequency for the variable speed drive oil pump is 45 Hz. This inhibit is released when the
compressor #1 motor current decreases to < 15% FLA and the
Clear Fault
button is pressed
on the Home screen. A complete 150 second coastdown is performed when after the inhibit
is released.
Motor #2 – Current >15%
FLA
The chiller (both compressors) is inhibited from starting because a motor current of >15%
FLA was detected on compressor #2 while it was not running. This inhibit is set instantly with
no delay and the oil pump is started as soon as the motor current is detected. The starting
frequency for the variable speed drive oil pump is 45 Hz. This inhibit is released when the
compressor #1 motor current decreases to < 15% FLA and the
Clear Fault
button is pressed
on the Home screen. A complete 150 second coastdown is performed when after the inhibit
is released.
Vanes #1 – Motor Switch
Open
The chiller (both compressors) is inhibited from starting because the pre-rotation vanes
of compressor #1 are not fully closed (Vane motor switch is open) and compressor #2 is
unable to run. This inhibit is released when the vanes have fully closed (Vane motor switch
has closed).
Vanes #2 – Motor Switch
Open
The chiller (both compressors) is inhibited from starting because the pre-rotation vanes of
compressor #2 are not fully closed (Vane motor switch is open) and compressor #1 is unable
to run. This inhibit is released when the Vanes have fully closed (Vane motor switch has
closed).
131
Model YD Mod D with OptiView Control Center
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...