Table 58: Display only fields
Field/LED name
Description
Oil pump 2: Oil pump run output
(LED)
Illuminates when compressor #2 Variable Speed Oil Pump is being commanded to
run.
Oil pump 2: Pump oil pressure
(HOP)
Displays the high-side oil pressure measured at the compressor #2 bearing input.
Oil pump 2: Oil pressure
Displays the pressure differential between the Pump oil pressure (HOP) transducer
for compressor #2 and the common Sump oil pressure (LOP) transducer. If this
compressor is the lead compressor, includes offset pressure derived from auto-
zeroing during compressor #2 Pre-lube. However, if compressor #1 is the lead
compressor, this value includes offset pressure derived from auto-zeroing during
compressor #1 Pre-lube (refer to auto-zeroing explanation under the Compressor
Screen). If either transducer used to calculate this differential is out of range, the
display field will show XX.X.
Oil pump 2: Oil pump drive
command frequency
Displays the speed command applied to compressor #2 Variable Speed Oil Pump.
Oil pump 2: Setpoint or target oil
pressure
Displays the oil pressure that compressor #2 Variable Speed Oil Pump is controlling
to. During the pre-lube and for the first 15 seconds of System Run, this is the Target
Setpoint and is fixed at 45.0 psid. For the remainder of compressor #2 run, it is the
programmed Setpoint Oil Pressure.
Oil pump 2: Pulldown time
remaining
Displays the time remaining until the user programmed Setpoint Oil Pressure is used.
While this clock is decrementing, the Target Oil Pressure Setpoint (fixed at 45.0 psid) is
in effect.
Oil level (bar graph)
Displays the oil level in the oil sump as a vertical graph. The range of the graph is
0% to 100%. Three colors are used as follows: 0% to 35% - red; >35% to 80% - green;
>80% to 100% - yellow. Only displayed if enabled using the Oil Level Detection (Enable/
Disable) key.
Table 59: Programmable
Button
Access level
Description
Oil level detection
(enable/disable) Service
Enables or disables the Oil Level Detection feature. When enabled, displays the oil level
in the oil sump as a vertical graph.
Table 60: Navigation
Button
Access level
Description
Home
View
Returns to the Home screen.
Oil pump 1
View
Displays a subscreen that allows manual control and programming of the setpoints for
compressor #1 Variable Speed Oil Pump.
Oil pump 2
View
Displays a subscreen that allows manual control and programming of the setpoints for
compressor #2 Variable Speed Oil Pump.
73
Model YD Mod D with OptiView Control Center
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...