Table 108: Programmable
Button
Access level
Description
3 Year Service
Warning
Test Op
Use this to enable or disable the 3 Year Service Warning feature. A service warning
appears as yellow in the System Details line when the 3 Year Service is due. The
warning clears when you press the Maintenance Acknowledge button and enter code
0726
.
Check Oil System
Warning
Test Op
Use this to enable or disable the Check Oil System Maintenance Warning. The warning
clears when you press the Maintenance Acknowledge button and enter code
0726
.
Condenser High
Small Temp
Difference
Warning
Test Op
Use this to enable or disable the Condenser High Small Temperature Difference
feature. A service warning appears as yellow in the System Detail line when the
Condenser High Small Difference Temperature exceeds the threshold setpoint. The
warning clears when you press the Maintenance Acknowledge button and enter code
0726
.
Table 109: Navigation
Button
Description
Maintenance Acknowledge
Acknowledges maintenance using the Maintainance Acknowledge password.
Home
Returns to the Home screen.
Setup
Returns to the Setup screen.
Diagnostics
Returns to the Diagnostics screen.
Model YD Mod D with OptiView Control Center
110
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...