Table 18: Display only fields
Field/LED name
Description
Oil pump drive command frequency Indicates the VSOP Drive Command Frequency, 0 Hz to 60 Hz.
Vane motor switch (LED) (open/
closed)
Lights when the compressor vanes are in the fully closed position. When Off, indicates
open.
Compressor status
Displays whether compressor has been selected as the lead or Lag compressor. The
lead compressor is selected upon receipt of a start signal. The compressor that has the
least amount of run time that is ready to run is selected as the lead compressor.
% Full load amps
Displays compressor motor current as a percentage of Full Load Amps of the
compressor motor.
PRV opening (LED)
Lights when an open command is being applied to the Pre-Rotation Vanes.
PRV closing (LED)
Lights when an close command is being applied to the Pre-Rotation Vanes.
PRV position
Displays the position (0% to 100%) of the pre-rotation vanes.
PRV command
Displays the position command (0% to 100%) for the pre-rotation vanes.
Discharge valve close command
(LED)
Lights when a close command is being applied to the compressor Discharge Valve.
Discharge valve open command
(LED)
Lights when an open command is being applied to the compressor Discharge Valve.
Discharge valve
Indicates the status of the compressor Discharge Valve as closing, closed, opening or
opened.
High pressure switch
Indicates the status of the compressor High Pressure Switch (open or closed).
Programmable
Software does not allow manual Pre-rotation Vanes control on a shutdown compressor while the
other compressor is running. This helps minimize rotation of this compressor if its Discharge Valve
is not fully sealed.
Table 19: Programmable
Button
Description
Discharge valve control mode
(manual/auto)
Only displayed if the compressor is stopped. This key puts the compressor Discharge
Valve in manual or automatic operation. When in manual operation, this key is used to
manually open or close the valve.
Table 20: Navigation
Button
Description
Home
Returns to the Home screen.
Compressor
Return to the Main Compressor screen.
VGD
Only displayed if VGD feature enabled on Operations Screen. Displays the subscreen
for viewing and programming of the Variable Geometry Diffuser (VGD) feature for the
compressor.
Proximity probe calibrate
Only available if chiller is stopped. Displays the subscreen that allows calibration of the
High Speed Thrust Bearing Proximity Probe for the compressor.
PRV calibrate
Only available if the chiller is stopped. Displays the subscreen that allows calibration
and manual control of the Pre-rotation Vanes for the compressor.
Capacity control
Displays the Capacity Control screen.
43
Model YD Mod D with OptiView Control Center
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...