
FORM 150.65-NM4
93
YORK INTERNATIONAL
FIELD INSTALLATION
If it becomes necessary to field install the Hot Gas
(Loadminder) Option, two kits are required. The part num-
bers of the kits are 375-04249-001 and 471-01232-101.
The 471-01232-101 kit consists of a second Relay Out-
put Board. It is not required if two Relay Boards are al-
ready installed in the control panel. If the 375-04249-001
kit is not available, the following parts should be ordered
separately.
DISCHARGE PRESSURE READOUT OPTION
The Discharge Pressure Readout Option P/N 471-01232-
131 allows the user to obtain control panel displays of
discharge pressure. Additionally, other displays such as
fault information will then hold relevant discharge pres-
sure information useful in diagnosing problems.
The discharge pressure unloading feature also becomes
usable when this option is installed (Page 44) as well as
fan cycling by discharge pressure.
Fan cycling by discharge pressure sometimes becomes
ITEM
QTY
PART #
DESCRIPTION
1
1
375-00431-025
SOL. VALVE
2
1
375-00431-026
SOL. VALVE
3
2
075-03742-000
SUPPORT
4
1
075-04281-000
PIPE CONN.
5
4
066-83964-000
CLAMP
6
2
075-04286-000
PIPE CONN.
7
4
066-88928-000
CLAMP
8
4
023-00200-000
REDUCER
9
1
075-04200-000
PIPE CONN.
10
1
075-04283-000
PIPE CONN.
11
1
075-04202-000
PIPE CONN.
12
1
075-03781-000
PIPE CONN.
13
1
075-04284-000
PIPE CONN.
14
4
021-16161-000
SCREW
15
20
021-16136-000
SCREW
16
4
021-16210-000
LOCKWASHER
17
2
023-08576-000
TEE
18
4
021-16151-000
HEX NUT
19
2
023-09743-000
E11
20
1
075-04285-000
TUBING
22
1
075-04282-000
PIPE CONN.
23
2
031-01117-000
SUPPRESSOR
24
2
023-05299-000
CLAMP
25
2
021-08381-000
SCREW
26
2
021-00451-000
HEX NUT
27
2
021-01148-000
LOCKWASHER
30
1
075-04201-000
PIPE CONN.
32
5
023-00061-000
COUPLING
33
4
075-04519-000
BRACKET
XX
1
075-04249-000
DRAWING
necessary, if ambient temperature cycling of fans causes
low suction pressure faults due to unusual operating
conditions or chiller location problems. Fan cycling by
discharge pressure only, allows higher discharge pres-
sures which in turn raises suction pressure by permit-
ting better operation of the thermal expansion valve. To
convert to discharge pressure cycling, the micro panel
must be programmed for DISCHARGE PRESSURE FAN
CONTROL (See Page 38). Fan cycling will operate as
indicated in Table 3.
TABLE 3 – FAN CYCLING
The kit consists of discharge pressure transducers for
each system, wire harnesses, and associated mounting
hardware.
HIGH AMBIENT OPTION
The High Ambient Option consists of two kits, P/Ns 471-
01232-131 and 475-23850-000. The option allows opera-
tion of the chiller in ambients up to 115°F (46.1°C). Typi-
cally, standard operation is limited to 105°F (40.6°C).
High ambient operation is accomplished by discharge
pressure unloading to assure that the chiller does not
fault due to the high pressure cutout opening during high
temperature operation. A sun shield is also installed on
the control panel to prevent direct sunlight from over-
heating the control panel causing subsequent malfunc-
tion of the electromechanical and electronic components
in the control panel. Additionally, actual discharge pres-
sure readouts can now be obtained from the micro panel.
Discharge Pressure unloading allows the microproces-
sor to unload a compressor when the discharge pres-
sure approaches a point nearing the discharge pressure
cutout. This assures that the system does not shut down
completely if the cutout were to open. See Page 44 for
programming the unloading pressure.
Fan cycling by discharge pressure is also available when
this option is installed (See DISCHARGE PRESSURE
READOUT OPTION this page), however it is of little use
in areas where ambients are generally high and stan-
dard temperature control of the fans provides good con-
trol and maximum efficiency.
SYS
FAN
CONTACTORS
ON
OFF
1 & 3 REV
(Optional
9M & 10M
320 PSIG
120 PSIG
Low Ambient)
(2.2 mPa) (827.4 kPa)
1
2 & 4
6M & 8M
340 PSIG
120 PSIG
(2.3 mPa) (827.4 kPa)
1 & 3 FWD
5M & 7M
360 PSIG
140 PSIG
(2.5 mPa) (965.3 kPa)
5 & 7 REV
(Optional
15M & 16M
320 PSIG
120 PSIG
Low Ambient)
(2.2 mPa) (827.4 kPa)
2
6 & 8
12M & 14M
340 PSIG
120 PSIG
(2.3 mPa) (827.4 kPa)
5 & 7 FWD
11M & 13M
360 PSIG
140 PSIG
(2.5 mPa) (965.3 kPa)
Summary of Contents for Millennium YCAJ150
Page 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Page 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Page 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Page 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Page 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Page 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Page 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Page 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Page 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Page 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...