FORM 150.65-NM4
31
YORK INTERNATIONAL
UNIT CONTROLS AND OPERATION
YORK MILLENNIUM CONTROL CENTER
FIG. 9 – MILLENNIUM CONTROL CENTER
INTRODUCTION
The YORK Millennium Control Center is a microproces-
sor based control system capable of multi-circuit control
to maintain chilled liquid temperature.
A 40 character display (2 lines of 20 characters) allows
the operator to display system operating parameters as
well as access programmed information already in
memory. A keypad for programming and accessing set-
points, pressures, temperatures, motor current, cutouts,
daily schedule, options, and fault information is provided.
A master ON/OFF switch is available to activate or de-
activate the chiller system. Separate system (SYS)
switches for each refrigerant system (up to 4) are pro-
vided on the Microprocessor Board.
Remote cycling, unloading, and chilled water tempera-
ture reset can be accomplished by user supplied dry
contacts.
Compressor starting/stopping and loading/unloading de-
cisions are performed by the Microprocessor to main-
tain leaving water temperatures. These decisions are a
function of temperature deviation from setpoint and rate
of change of temperature.
MICROPROCESSOR BOARD
The Microprocessor Board is the controller and decision-
maker in the control panel. System inputs from pres-
sure transducers, temperature sensors, and C.T.s are
connected directly to the Microprocessor Board. The Mi-
croprocessor Board circuitry multiplexes these analog
inputs, digitizes them, and constantly scans them to
keep a constant watch on the chiller operating condi-
tions. From this information, the Microprocessor then
issues commands to the Relay Output Board to control
contactors, solenoids, etc. for water temperature con-
trol and to react to safety conditions.
Keypad commands are acted upon by the micro to
change setpoints, cut-outs, scheduling, operating re-
quirements, and to provide displays.
A +12V REG supply voltage from the Power Supply Board
is converted to +5V REG by a voltage regulator located
on the Microprocessor Board. This voltage is used to
operate integrated circuitry on the board.
Four system switches located on the Microprocessor
Board activate or deactivate the individual systems (com-
pressors).
02711TG
Summary of Contents for Millennium YCAJ150
Page 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Page 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Page 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Page 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Page 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Page 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Page 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Page 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Page 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Page 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...