FORM 150.65-NM4
13
YORK INTERNATIONAL
LEGEND:
VOLT
= Voltage
MCA
= Minimum Circuit Ampacity
DISC
= Disconnect
N/A
= Not Available
CPR-RLA
= Compressor Running Load Amps
CPR-RLA
= Compressor Part Winding Inrush Amps
FLA
= Full Load Amps
CKT BRK
= Circuit Breaker
HACR
= Heating, Air Conditioning and Refrigeration
SINGLE POINT POWER SUPPLY WIRING (OPTIONAL)
SYSTEM #1
SYSTEM #2
MODEL
MIN
2
YCA
MCA
1
DUAL ELEM
NF
INCOMING
YORK SUPPLIED DISCONNECT
CPR
CPR
FAN
CPR
CPR
FAN
FUSE
DISC
WIRE RANGE
5
(CU ONLY)
5
RLA
LRA
8
FLA
RLA
LRA
8
FLA
MIN
3
MAX
3
SW
(CU ONLY)
J150
-46
335
400
450
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
131
525
5.0
131
525
5.0
J150
-58
275
350
350
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
105
420
4.9
105
420
4.9
J160
-46
376
450
500
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
164
639
5.0
131
525
5.0
J160
-58
308
350
400
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
131
511
4.9
105
420
4.9
J180
-46
409
500
500
600
(2) #2 - 600
(3) 3/0 - 500
164
639
5.0
164
639
5.0
J180
-58
334
400
450
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
131
511
4.9
131
511
4.9
J190
-46
439
500
600
600
(2) #2 - 600
(3) 3/0 - 500
188
639
5.0
164
639
5.0
J190
-58
358
400
500
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
150
511
4.9
131
511
4.9
J200
-46
488
600
600
600
(2) #2 - 600
(3) 3/0 - 500
188
639
8.1
188
639
8.1
J200
-58
385
450
500
400
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
150
511
5.9
150
511
5.9
J220
-46
538
600
700
600
(2) #2 - 600
(3) 3/0 - 500
228
936
8.1
188
639
8.1
J220
-58
425
500
600
600
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
182
749
5.9
150
511
5.9
J230
-46
578
700
800
600
(2) #2 - 600
(3) 3/0 - 500
228
936
8.1
228
936
8.1
J230
-58
457
600
600
600
(2) #2 - 600
(1) #1 - 600 or (2) #1 - 250
182
749
5.9
182
749
5.9
5. Wire Range is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (1), (2), or (3) preceding the
wire range indicates the number of termination points available per phase. The (1-2) preceding the wire range indicates that a single
double-barreled lug is available per phase that can accept up to two wires of the wire range specified. “(1) #1-600 or (2) #1-250”
indicates that a single lug is supplied and it will accept a single wire up to 600MCM or 2 wires up to 250MCM. Actual wire size and number
of wires per phase must be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above
recommendations are based on the National Electrical Code and using copper connectors only. Field wiring must also comply with local
codes.
6. A ground lug is provided for each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM (104 - 220 Tons)(334 - 810 kW).
7. The supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
8. All unit compressors have a part winding electrical configuration such that the indicated Locked Rotor Amps are Part Wind Locked Rotor
Amps.
Summary of Contents for Millennium YCAJ150
Page 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Page 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Page 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Page 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Page 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Page 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Page 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Page 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Page 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Page 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...