FORM 150.65-NM4
23
YORK INTERNA
TIONAL
CAUTION:
No Controls (relays,
etc.) should be
mounted in the Smart
Panel enclosure or
connected to power
supplies in the control
panel. Additionally, con-
trol wiring not con-
nected to the Smart
Panel should not be run
through the cabinet.
This could result in nui-
sance faults.
CAUTION:
Any inductive devices
(relays) wired in series
with the flow switch for
start/stop, into the
Alarm circuitry, or pilot
relays for pump start-
ers wired through mo-
tor contactor auxiliary
contacts must be sup-
pressed with YORK
P/N 031-00808-000
suppressor across the
relay/contactor coil.
Any contacts con-
nected to flow switch
inputs or BAS inputs on
terminals 13 - 19 or
TB3, or any other ter-
minals, must be sup-
pressed with a YORK
P/N 031-00808-000
suppressor across the
relay/contactor coil.
CAUTION:
Control wiring con-
nected to the control
panel should never be
run in the same con-
duit with power wiring.
FIG. 6 – ELEMENTARY DIAGRAM (Cont’d)
LD02459
CONTROL POWER SUPPLY
MAXIMUM
NON-FUSED
UNIT
CONTROL
MINIMUM
DUAL-
DISC.
VOLTAGE
POWER
CIRCUIT
ELEMENT
SWITCH
SUPPLY
AMPACITY
FUSE SIZE
SIZE
Standard
Models without
115-1-60
20A
20A, 250V
30A, 240V
Transformers
Summary of Contents for Millennium YCAJ150
Page 21: ...FORM 150 65 NM4 21 YORK INTERNATIONAL LD02461 FIG 6 ELEMENTARY DIAGRAM Cont d...
Page 22: ...22 YORK INTERNATIONAL ELEMENTARY DIAGRAM...
Page 24: ...24 YORK INTERNATIONAL CONNECTION DIAGRAM FIG 7 CONNECTION DIAGRAM LD02463...
Page 25: ...FORM 150 65 NM4 25 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02462...
Page 30: ...30 YORK INTERNATIONAL FIG 8 SYSTEM WIRING Cont d LD02499...
Page 100: ...100 YORK INTERNATIONAL LD02654 FIG 37B LOUVER BRACKETS INSTALLATION...
Page 103: ...FORM 150 65 NM4 103 YORK INTERNATIONAL LD02656 FIG 39A LOUVER INSTALLATION SIDES...
Page 104: ...104 YORK INTERNATIONAL LD02654 FIG 39B LOUVER BRACKETS INSTALLATION...
Page 108: ...108 YORK INTERNATIONAL FIG 40B CONDENSER COIL LOUVER INSTALLATION FRONT AND BACK LD02659...
Page 110: ...110 YORK INTERNATIONAL FIG 41 REMOTE RESET BOARD LD02666 P1...