Compressor won’t
5. Faulty wiring to loading solenoid.
5. Check wiring.
load
6. Defective water temperature sensor.
6. Compare sensor with a thermometer. Var-
(Cont’d)
iation of sensor vs. thermometer of +/–2°F
is not unusual. Replace if necessary.
7. Defective evaporator or optional
7. Replace transducer after verifying with a
discharge transducer.
gauge.
Lack of Cooling
1. Fouled evaporator surface.
1. Contact the local YORK service represen-
Effect
tative.
2. Faulty compressor suction and / or
2. Contact the local YORK service represen-
charge valves.
tative.
PROBLEM
CAUSE
SOLUTION