1. System Installation Requirements
1-21
TI 33J01J10-01EN
n
Grounding when joining CENTUM VP side by side with other system
Do not connect CENTUM VP’s cabinet with other cabinets electrically using bolts or other
connection mechanism in order to avoid unexpected electrical connection or interference.
When CENTUM VP is joining side by side with other cabinets, ensure to insert insulating sheets.
The cabinets other than CENTUM VP must be insulated from a floor and connect it to a
protective grounding system using a different grounding cable.
The CENTUM VP system in this page can also be read as cabinet of CENTUM CS 3000,
CENTUM CS, or ProSafe-RS.
CAUTION
Do not install the following systems side-by-side with CENTUM VP:
• Systems using power supply voltages over 300 V AC.
• Systems with current consumption over 50 A.
• System containing high frequency sources.
G
Equipmment
F010405.ai
Grounding bus inlte
Protective grounding system
Insulating sheet
Insulating sheet
CENTUM VP
CENTUM VP
G: Grounding Bar
G
Other system
Cabinet
/Console Type
HIS
Cabinet
/Console Type
Insulating sheet material:
Thickness:
PVC or
PL-PEV, PL-PEM Bakelite
5-10 mm
Figure Grounding Using Insulating Sheets
TIP
The CENTUM VP cabinets (e.g. AFV40S/AFV40D, and ACB51) are insulated from the floor by the insulating
sheet.
When other cabinets and consoles are used with CENTUM VP, insulate them from the floor using the insulating
sheets.
Apr. 21, 2017-00