3. Cabling
3-4
TI 33J01J10-01EN
n
Cable Terminals
Use the specified solderless terminals and sleeves for pressure clamp terminal on the end of
terminal-connected cables, providing low contact resistance, high durability, and low aging.
l
Solderless Lug
CAUTION
• Be sure to use solderless terminals with insulating sheath.
• Use solderless terminals and crimp tools from the same maker.
• Use different crimp tools according to cable size.
F030101.ai
Figure Solderless Terminal with Insulating Sheath
l
Sleeve for pressure clamp terminal and spring clamp terminal
When connecting the process I/O signal to the pressure clamp terminal of FIO and N-IO, strip the
cable coating (without a sleeve) or attach a sleeve to the cable.
Signal cable
Signal cable
Without sleeve
With sleeve
Sleeve with insulating
cover
Sleeve without insulating
cover
F030102.ai
Figure Sleeve for Pressure Clamp Terminal
CAUTION
• Use a sleeve and a clamp tool from the same manufacturer.
• Use a sleeve and a clamp tool which suit the cable thickness.
• Use a sleeve which meet the DIN 46228 standards.
n
Bending radius of the cable
When connecting a cable to a system instrument, ensure to secure the minimum bending radius
of the cable.
The minimum bending radius is either the value shown in the cable manufacturer’s specifications
or six-fold of the cable conductor diameter, whichever is bigger should be applied.