![YOKOGAWA CENTUM CS Technical Information Download Page 65](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927065.webp)
2. Transportation, Storage and Installation
2-21
TI 33J01J10-01EN
2.5.4
DIN Rail Mountable Devices
The following devices can be mounted to a DIN rail.
Node interface unit: A2NN30D-
0
Adaptor base plate: A2BN3D-0
Barrier base plate: A2BN4D-2
A2BN5D-2
Power supply unit: A2PW503/DN, A2PW504/DN
Terminal board: A2BM4
IMPORTANT
Install a DIN rail mountable device inside a metal cabinet.
Installation inside a metal cabinet with a lock is required to comply with standards; in particular,
safety standards and EMC conformity standards.
n
Notes on Installation
CAUTION
For installation, secure ample working space and work in a team for safety.
l
Provide Space for Mounting
A2NN30D, A2BN3D, and A2BN5D need to be slide when they are mounted on the DIN rail. For
that reason, provide a space shown in the following figure. Refer to the General Specifications
(GS) for the external dimensions.
F020523.ai
+10 mm
Providing a space for mounting
on the right side of the unit
Unit
mountiong position
+10 mm
Providing a space for mounting
above the unit
Node Interface Unit:
A2NN30D-
0
Unit: A2BN3D-0
Node interface Unit
mounting position
+10 mm
Unit
mountiong position
Unit: A2BN5D-2
+10 mm
Providing a space for mounting
on the both sides of the unit
Figure Providing a Space for Mounting (Front View)
Oct. 5, 2018-00
Summary of Contents for CENTUM CS
Page 2: ...Blank Page...