Breaker Specifications
Breaker ratings are listed below:
Table Breaker Ratings
Equipment
Built-in breaker
rating (A/V)
External breaker
rating (Recommend)
(A/V) (*1)
A2FV50S/A2FV50D field control unit (100 V AC, 220 V AC)
6.3/250 (fuse)
15/250
A2FV50S/A2FV50D field control unit (24 V DC)
10/250 (fuse)
20/250
A2FV70S/A2FV70D field control unit (100 V AC, 220 V AC)
6.3/250 (fuse)
15/250
A2FV70S/A2FV70D field control unit (24 V DC)
10/250 (fuse)
20/250
ANB10S/10D ESB bus node unit (100 V,220 V AC)
6.3/250 (fuse)
15/250
ANB10S/10D ESB bus node unit (24 V DC)
10/250 (fuse)
20/250
AFV30S/D field control unit (100 V AC system)
6.3/250 (fuse)
15/250
AFV30S/D field control unit (220 V AC system)
6.3/250 (fuse)
15/250
AFV30S/D field control unit (24 V DC)
10/250 (fuse)
20/250
AFV40S/D field control unit (100 V AC system)
20/250 (two)
50/250
AFV40S/D field control unit (220 V AC system)
20/250 (two)
50/250
AFV40S/D field control unit (24 V DC)
30/24 (three)
100/24
ACB51 I/O expansion cabinet (100 V AC system)
20/250 (two)
50/250
ACB51 I/O expansion cabinet (220 V AC system)
20/250 (two)
50/250
ACB51 I/O expansion cabinet (24 V DC)
30/24 (three)
100/24
ANB11S/D Optical ESB bus node unit (100 V AC system)
6.3/250 (fuse)
15/250
ANB11S/D Optical ESB bus node unit (220 V AC system)
6.3/250 (fuse)
15/250
ANB11S/D Optical ESB bus node unit (24 V DC)
10/250 (fuse)
20/250
ANT10U Unit for optical ESB bus repeater module (100 V AC system)
6.3/250 (fuse)
15/250
ANT10U Unit for optical ESB bus repeater module (220 V AC system)
6.3/250 (fuse)
15/250
ANT10U Unit for optical ESB bus repeater module (24 V DC)
10/250 (fuse)
20/250
ACUKT1 Cabinet utility kit (100 V AC system)
20/250 (fuse)
50/250
ACUKT1 Cabinet utility kit (220 V AC system)
20/250 (fuse)
50/250
ACUKT1 Cabinet utility kit (24 V DC)
30/24 (three)
100/24
AVR10D Duplexed V net router (100 V AC system)
3.15/250 (fuse)
10/250
AVR10D Duplexed V net router (220 V AC system)
3.15/250 (fuse)
10/250
AVR10D Duplexed V net router (24 V DC)
6.3/250 (fuse)
15/250
AW810D Wide Area Communication Router (100 V AC system)
3.15/250 (fuse)
10/250
AW810D Wide Area Communication Router (220 V AC system)
3.15/250 (fuse)
10/250
AW810D Wide Area Communication Router (24 V DC)
6.3/250 (fuse)
15/250
A2NN10D Node Interface Unit (100-240 V AC system)
5/250 (fuse)
15/250
A2NN10D Node interface Unit (24 V DC)
12/250 (fuse)
30/24
A2NN30D Node Interface Unit (100-240 V AC system)
5/250 (fuse)
15/250
A2NN30D Node interface Unit (24 V DC)
12/250 (fuse)
30/24
A2PW503 Power Supply Unit (100-240 V AC system )
5/250
15/250
A2PW504 Power Supply Unit (24 V DC)
12/250
30/24
A2BN4D Base Plate for Barrier (MTL): Barrier Power Input (24 V DC)
2.5/250 (fuse)
—
A2BN5D Base Plate for Barrier (P+F): Barrier Power Input (24 V DC)
2/250 (fuse)
—
*1: