![YOKOGAWA CENTUM CS Technical Information Download Page 205](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927205.webp)
3. Cabling
3-107
TI 33J01J10-01EN
n
Signal connection of a terminal block for the multichannel I/O module
The signal cables of the field devices to the terminal blocks for the multi-channel I/O module must
be connected to different terminals depending on the types of signals. To prevent damage to
devices, connect signal cables to the appropriate terminals according to the type of signals.
The following table shows the relationship between signal types and terminal numbers of
channels.
Table Terminal numbers and signal types - Analog I/O module
I/O modules
Terminal
number
(*1)
Signal types
Device
Model and suffix code
Analog input module
AAI143-HM
A
Current input +
B
Current input -
Analog output
module
AAI543-HM
A
Current
B
Current output -
RTD/POT input
module(*
2)
AAR145-SM
A
RTD input A (*3)
B
RTD input B
B
RTD input B (*3)
TC/mV input module
AAT145-SM
A
TC/mV input +
B
TC/mV input -
Analog input module
AAV144-SM
A
Voltage input +
B
Voltage input -
*1:
: 1 to 16
*2: POT input is not supported.
*3: The resistance values of the connecting cables must match.
Table Terminal numbers and signal types - Digital I/O module
I/O modules
Terminal
number
(*1)
Signal types
Device
Model and suffix code
ST3-compatible
digital input module
ADV159-PM
A
Status input +
Push button input +
B
Status input -
Push button input -
ADV159-PY
A
Relay status input +
Relay push button
input
+
B
Relay status input -
Relay push button
input -
C
—
—
ST6-compatible
digital input module
ADV169-PM
A
Status input +
Push button input +
B
Status input -
Push button input -
Oct. 5, 2018-00
Summary of Contents for CENTUM CS
Page 2: ...Blank Page...