4. Installation Specifications
4-11
TI 33J01J10-01EN
June 30, 2016-00
l
AFV40
, ACB51
Table Periodic Replacement Parts Having Defined Life Spans
Part
names
Part
numbers
Recommended
replacement
cycle
Used
in:
Replacement
by user
Remarks
A
F
V
4
0
A
C
B
5
1
Power Supply
Module
(100-120 V AC)
PW481
8 years
x
x
Yes
Average ambient temperature 40
°C or less
Power Supply
Module
(220-240 V AC)
PW482
8 years
x
x
Yes
Average ambient temperature 40
°C or less
Power Supply
Module
(24 V DC)
PW484
8 years
x
x
Yes
Average ambient temperature 40
°C or less
Power Supply Unit
for Fan
(100-120 V AC,
220-240 V AC)
S9618FA
8 years
x
x
Yes
Average ambient temperature 40
°C or less
Power Supply
Unit for Fan
(24 V DC)
S9619FA
8 years
x
x
Yes
Average ambient temperature 40
°C or less
Battery Pack
S9548FA
3 years
x
Yes
Average ambient temperature 30
°C or less
1.5 years
x
Yes
Average ambient temperature 40
°C or less
9 months
x
Yes
Average ambient temperature 50
°C or less
Aluminium
Electrolytic
Capacitor
(in power
supply module)
(PW481)
8 years
x
x
No
100 V AC:Average ambient temperature
40°C or less
(PW482)
8 years
x
x
No
220 V AC:Average ambient temperature
40°C or less
(PW484)
8 years
x
x
No
24 V DC:Average ambient temperature
40°C or less
Air Filter
T9070CB
1 years
x
x
Yes
For Door fan unit
Fan Unit
AIP601
4 years
x
x
Yes
For Door fan unit
AIP611
4 years
x
x
Yes
For Node fan unit
Built-in power fuse
—
8 years
x
x
No
For PW481, PW482, PW484