3. Cabling
3-106
TI 33J01J10-01EN
l
Dual-redundant current output
For current signal output, adaptors can be configured for redundancy. Mount the adaptors in the
slots that are vertically next to one another, and set the signal setting of the adaptors in the odd-
numbered slot and the even-numbered slot to dual-redundant.
To also match the output, connect terminal A to terminal A, and terminal C to terminal C on the
terminal blocks by using short-bars (Part number: A1534JT).
The following figure shows how to attach short-bars by using an example of a dual-redundant
configuration of adaptors in slots 3 and 4.
A2SAM505
A2SAM505
3A
4A
3C
4C
3B
4B
Terminal block
Slots for adaptors
Slot 3
Slot 4
F030806.ai
Figure Example of attaching short-bars
TIP
When using the ELCO connector, short the pins that correspond to terminal A on a terminal block, and the pins
that correspond to terminal C.
SEE
ALSO
For more information about the ELCO connector pin assignment, refer to:
"N-IO Node (for RIO System Upgrade)" (GS 33J64F10-01EN)