2. Transportation, Storage and Installation
2-18
TI 33J01J10-01EN
l
Providing Area for Servicing
When mounting devices in the 19-inch rack, the mounting plate cut out of instrumentation panel,
and so on, leave an area for servicing.
Leave an area for servicing.
• All the work to connect cables to 19-inch rack mountable devices and I/O modules will be
performed from the front.
• The work to confirm indicator lamps, configure card settings, and remove/insert cards will be
performed from the front.
• The front is the area for wiring and servicing. Leave at least 1000 mm of space at the front.
F020511.ai
Ceiling
Ventilation fan
Front
Servicing area
3 units or more
50 mm or more
100 mm or more
1000 mm or more
19-inch rack, or mounting plate
cut out of the instrumentation panel
Figure Space Required for Rack-mount Equipment
Apr. 21, 2017-00