3. Cabling
3-61
TI 33J01J10-01EN
3.6.2
List of Signal Cables for Connection with FIO
The following table shows the list of signal cables connections with FIO.
Table Signal Cables for Connection with FIO (1/3)
Module
Name
I/O channels
per Module
Connection Signal
Pressure
Clamp
Terminal
Yokogawa-
specific
Cable (*1)
MIL
Cable
Analog I/O Modules
AAI141
Analog Input Module (4 to 20 mA, Non-Isolated)
16
x
x
x
AAV141 Analog Input Module (1 to 5 V, Non-Isolated)
16
x
x
x
AAB141
Analog Input Module
(1 to 5 V / 4 to 20 mA, Non-Isolated)
16
–
x
–
AAI841
Analog I/O Module
(4 to 20 mA Input, 4 to 20 mA Output, Non-Isolated)
8 input/8 output
x
x
x
AAB841
Analog I/O Module
(1 to 5 V Input, 4 to 20 mA Output, Non-Isolated)
8 input/8 output
x
x
x
AAB842
Analog I/O Module
(1 to 5 V / 4 to 20 mA Input, 4 to 20 mA Output,
Non-Isolated)
8 input/8 output
–
x
–
AAI143
Analog Input Module (4 to 20 mA, Isolated)
16
x
x
x
AAI543
Analog Output Module (4 to 20 mA, Isolated)
16
x
x
x
AAV144 Analog Input Module (-10 to +10 V, Non-Isolated)
16
x
x
x
AAV544 Analog Output Module
(-10 to +10 V, Non-Isolated)
16
x
x
x
AAI135
Analog Input Module
(4 to 20 mA, Isolated Channels)
8
x
x
x
AAI835
Analog I/O Module (4 to 20 mA, Isolated Channels)
4 input/4 output
x
x
x
AAT145
TC/mV Input Module (TC: R, J, K, E, T, B, S, N
/mV: -100 to 150 mV, Isolated Channels)
16
–
x (*2)
–
AAR145
RTD/POT Input Module (RTD: Pt100 Ω / POT: 0 to 10
kΩ, Isolated Channels)
16
–
x (*2)
–
AAP135 Pulse Input Module
(Pulse Count, 0 to 10 kHz, Isolated Channels)
8
x
x
x
AAP149 Pulse Input Module for compatible PM1
(Pulse Count, 0 to 6 kHz, Non-Isolated)
16
–
x
–
AAP849
Pulse Input/Analog Output module for compatible PAC
(Pulse Count input, 4 to 20 mA output, Non-Isolated)
8 input/8 output
–
x
–
x :
Can be connected.
– :
Cannot be connected.
*1:
Yokogawa-specific cable for connecting I/O Module and a terminal board, etc.
*2:
Can be connected directly with a Yokogawa-specific cable, without a terminal block.