![YOKOGAWA CENTUM CS Technical Information Download Page 98](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927098.webp)
2. Transportation, Storage and Installation
2-54
TI 33J01J10-01EN
2.5.7
Desktop Equipment
There are PCs, printers, etc. as the devices used on the desks.
When installing any devices on the desks, take care the followings:
• It should provide a level horizontal surface for the PC or the printer.
• A work space should be preserved to connect the cables.
• Support rising cables to prevent their weight from being applied to connectors directly.
Keep a space of 100 mm radius or more around the connectors.
• Do not place the desk such as to expose the PC to direct sunlight or high humidity.
2.5.8
Installing Control Bus Interface Card
This section describes how to install VI702 Control Bus interface card. The card is
installed in the PCI Express slot of a IBM PC/AT compatible PC to connect it to the Control
Bus. The card permits you to use CENTUM VP system operation and monitoring functions
on the PC when used with the dedicated software.
SEE
ALSO
• The steps described below are based on a common IBM PC/AT compatible machine. Refer to the manual
of the PC to be used for precise instructions.
• For station address setting, refer to “Peripherals Manual (A4. Control Bus Interface Card)” (IM
33J50B10-01EN).
l
Card Installation Procedure
1. Set a station address for the Control Bus interface card.
2. Turn off the computer and unplug the power cord to ensure safety.
3. Remove the PC cover.
4. Remove the slot cover.
5. Insert the Control Bus interface card in the slot. Make certain that the card is properly set in
the slot.
6. Attach the PC cover.
7. Write the station address on a seal (sticker) and attach it to the front of the PC or a similar
highly-visible place.
SEE
ALSO
For electrostatic protection, refer to Item 1.5.2, “Countermeasures against Static Electricity.”