4. Installation Specifications
4-3
TI 33J01J10-01EN
n
Actual Power-On In-Rush Current of Each Component
Actual in-rush current data measured for each component is listed below:
Table System Equipment Power-On In-Rush Current
Model
In-Rush current (A) In-Rush current (A) In-Rush current (A)
100 V AC
220 V AC
24 V DC
Primary Secondary Primary Secondary Primary Secondary
AFV30S
FCU (rack mountable type)
62
5
124
5
30
23
AFV30D
Duplexed FCU (rack mountable type)
62
5
124
5
30
23
AFV40S
FCU with Cabinet
(with Maximum no. of node units installed)
344
180
540
132
120
170
AFV40D
FCU with Cabinet
(with Maximum no. of node units installed)
344
180
540
132
120
170
A2FV50S
FCU (19-inch rack mountable type)
62
5
124
5
30
23
A2FV50D
Duplexed FCU
(19-inch rack mountable type)
62
5
124
5
30
23
A2FV70S/D FCU (rack mountable type)
62
5
124
5
30
23
AVR10D
Duplexed V net router
47
1
48
0.5
10
2
ACB51
I/O Expansion Cabinet
(With maximum no. of node units installed)
344
180
540
132
120
170
ANB10S/D
Node Unit for ESB Bus
62
5
124
5
30
23
ANB11S/D
Optical ESB Bus Node Unit
62
5
124
5
30
23
AVR10D
Duplexed V net Router
47
1
48
0.5
10
2
AW810D
Wide Area Communication Router
47
1
48
0.5
10
2
A2NN10D
Node Interface Unit
40
—
80
—
60
—
A2NN30D
Node Interface Unit
40
—
80
—
60
—
A2PW503
Power Supply Unit (100-240 V AC)
20
—
40
—
—
—
A2PW504
Power Supply Unit (24 V DC)
—
—
—
—
30
—
—
: There are no specifications.
Input current peak values and waveforms, influenced by input impedance, varies with system
configurations, line sharing with other systems, and other factors. The rush current data shown
above were measured under predetermined conditions (see below). Please note that the values
are subject to change.
The power input circuit, with an in-rush current limiting circuit, restrains primary in-rush current,
turning any current exceeding the limit to secondary and successive rush current.
l
Measurement Conditions
Input voltage: 132/264 V AC, 50 Hz, and 24 V DC
Power line impedance: Approx. 0.4 ohms (external line and internal impedance)
Turn-on timing: At 50 Hz, 90° or 5 ms after the AC zero-crossing point
(60 Hz data are almost identical to the 50 Hz data shown above.)
Measurement: The primary peak and secondary peak are measured after turn-on.
l
Note
• The timing of the maximum primary/secondary in-rush current varies with devices.
• The restart in-rush current after a momentary power failure exceeds the above data and its
timing is also different.
• For a system composed of multiple pieces of equipment, the in-rush current is normally
smaller than the total of the in-rush currents by individual pieces of equipment.