3. Cabling
3-98
TI 33J01J10-01EN
l
When receiving dry contact signals (Input frequency: 0 to 10 kHz)
Select "Without Shunt Resistor" (SW1: OFF) in the IOM builder. Also install two 510 Ω shunt
resistor modules on the shunt resistor unit. The total resistance value will be 1.02 kΩ.
The following figure shows the circuit diagram.
F030810.ai
FIL
IN
A
IN
B
IN
C
Transmitter
A2SAP105
4 kΩ
SW2
12 V DC/24 V DC
1.02 kΩ
SW1
DIN rail
Signal Line
Shunt resistor unit
(A2EXR001)
Terminal block of A2BA3D
Shunt resistor module
A
B
510Ω
510Ω
IN
B
IN
C
IN
A
:
1 to 16
Figure When receiving dry contact signals (Input frequency: 0 to 10 kHz)
•
Shunt Resistor Unit (A2EXR001)
SEE
ALSO
For the General specifications of A2EXR001, refer to N-IO Node (For RIO System Upgrade )
(GS 33J64F10-01EN)
The shunt resistor unit (Model: A2EXR001-S000030/KFR) converts the current signals of the
internal circuit of the pulse input signal adaptor into voltage signals and is capable of converting
four points of signals. It is used when receiving dry contact signal inputs with 0 to 10 kHz input
frequencies or current pulse signal inputs.