![YOKOGAWA CENTUM CS Technical Information Download Page 161](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927161.webp)
3. Cabling
3-63
TI 33J01J10-01EN
Table Signal Cables for Connection with FIO (3/3)
Module
Name
I/O channels
per Module
Connection Signal
Pressure
Clamp
Terminal
Yokogawa-
specific
Cable (*1)
MIL
Cable
Analog I/O Modules with Built-in Barrier
ASI133
Analog Input Module (4 to 20 mA, Isolated)
8
x
–
–
ASI533
Analog Output Module (4 to 20 mA, Isolated)
8
x
–
–
AST143
TC/mV Input Module (TC: B, E, J, K, N, R, S, T / mV:
-100 to 150 mV, -50 to 75 mV, Isolated)
16
x
–
–
ASR133
RTD/POT Input Module (RTD: Pt50, Pt100, Pt200,
Pt500, Pt1000, Ni100, Ni200, Ni120 / POT: 0 to 10
kΩ,Isolated)
8
x
–
–
Digital I/O Modules with Built-in Barrier
ASD143 Digital Input Module (NAMUR compatible, Isolated)
16
x
–
–
ASD533 Digital Output Module (Isolated)
8
x
–
–
Turbomachinery I/O Modules
AGS813
Servo Module (Isolated)
12
–
x (*4)
–
AGP813 High Speed Protection Module (Isolated)
26
–
x (*4)
–
x :
Can be connected.
– :
Cannot be connected.
*1:
Yokogawa-specific cable for connecting I/O Module and a terminal board, etc.
*4:
Available cables are AKB337-M005, M007 and M010.
CAUTION
When connecting a Yokogawa-specific cable to an FIO module, ensure to keep the minimum
bending radius of the cable. The minimum bending radius of the Yokogawa specific cable is six-
fold of the diameter of the cable.
Oct. 5, 2018-00
Summary of Contents for CENTUM CS
Page 2: ...Blank Page...
Page 246: ...Blank Page...