4. Installation Specifications
4-1
TI 33J01J10-01EN
4. Installation Specifications
This section summarizes power consumption, in-rush current, breaker ratings, parts
durability and other data for the installation of CENTUM VP system.
n
Electrical Specifications
Power consumption (current) and other electrical data are shown below:
Table Electrical Specifications (1/2)
Equipment
Input-voltage range
Max. power
consumption
(VA, A) (*1)
Heating
value J/h
(*2)
Voltage (V AC) Frequency (Hz)
AFV30S Field Control Unit
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
AFV30D Duplexed Field Control Unit
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
AFV40S Field Control Unit
(at maximum installation of FIO)
100-120
50/60±3
2500 VA
5400 × 10
3
(1500 W)
220-240
2860 VA
24 V DC
71 A
AFV40D Duplexed Field Control Unit
(at maximum installation of FIO)
100-120
50/60±3
2500 VA
5400 × 10
3
(1500 W)
220-240
2860 VA
24 V DC
71 A
A2FV50S 19-inch Rack Mountable Type Field
Control Unit for FIO
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
A2FV50D 19-inch Rack Mountable Type Duplexed
Field Control Unit for FIO
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
A2FV70S Field Control Unit
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
A2FV70D Field Control Unit
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
ANB10S ESB Bus Node Unit
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 × 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
ANB10D Duplexed ESB Bus Node Unit
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 x 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
ANB11S Node Unit for Single ESB Bus with Optical
Repeater
(at maximum installation of FIO)
100-120
50/60±3
200 VA
432 x 10
3
(120 W)
220-240
230 VA
24 V DC
5.5 A
June 30, 2016-00
*1:
Power consumption in steady operation is indicated in VA (AC) or A (DC). When power consumption varies according to the
installed number of equipment, power consumption by the maximum number of units installed is listed.
*2:
Heating value in steady operation is indicated in Joule/hour. When heating value varies according to the installed number of
equipment, heating value by the maximum number of units installed is listed.