![YOKOGAWA CENTUM CS Technical Information Download Page 202](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927202.webp)
3. Cabling
3-104
TI 33J01J10-01EN
The following figure shows how to install the shunt resistor module.
F030804.ai
Shunt resistor module
(A1080RZ)
Ring terminal
Terminal C
Terminal B
Ring terminal
Cable connecting to terminal B
Cable connecting to terminal C
A
B
C
Figure Installing the shunt resistor module
Follow these steps to install the shunt resistor module on the terminal block:
1. Open the cover of the terminal block.
2. Loosen the M4 screws of terminals B and C.
3. Insert the ring of the ring terminal of the cable that connects to terminal B into the gap.
Be sure to insert it with the convex side of the crimping part of the ring terminal being
oriented to the terminal block side.
4. Orient the shunt resistor module as shown in the figure and insert it into each gap of
terminals B and C.
The screw goes into the screw hole of the ring terminal and is secured temporarily.
5. Insert the ring of the ring terminal of the cable that connects to terminal C into the gap.
Be sure to insert it with the convex side of the crimping part of the ring terminal being
oriented in the opposite orientation of the shunt resistor module.
6. Tighten the M4 screws on terminals B and C.
7. Close the cover of the terminal block.
Oct. 5, 2018-00