2.7 H: Terminal Functions
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
171
2.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
u
H1: Contact Inputs
n
H1-02 to H1-16: Functions for Contact Inputs 2 to 16
These parameters assign functions to the contact inputs. The various functions and settings are listed below in
Table 2.20 Contact Input Parameters
Table 2.21 Contact Input Terminal Settings
No.
<1> The default setting is set to 73 and cannot be changed under the following conditions.
y
The drive software version is S0108 and later.
y
o2-09 is set to 2.
Name
Setting Range
Default
H1-02
Contact Input 2 Function Selection
1 to 9F
40: Forward Run Command (2-Wire Sequence)
H1-03
Contact Input 3 Function Selection
0 to 9F
6A: Drive Enable
H1-04
Contact Input 4 Function Selection
0 to 9F
70: Drive Enable 2
H1-05
Contact Input 5 Function Selection
0 to 9F
F: Through Mode
H1-06
Contact Input 6 Function Selection
0 to 9F
F: Through Mode
H1-07
Contact Input 7 Function Selection
0 to 9F
F: Through Mode
H1-08
Contact Input 8 Function Selection
0 to 9F
F: Through Mode
H1-09
Contact Input 9 Function Selection
0 to 9F
F: Through Mode
H1-10
Contact Input 10 Function Selection
0 to 9F
F: Through Mode
H1-11
Contact Input 11 Function Selection
0 to 9F
F: Through Mode
H1-12
Contact Input 12 Function Selection
0 to 9F
F: Through Mode
H1-13
Contact Input 13 Function Selection
0 to 9F
F: Through Mode
H1-14
Contact Input 14 Function Selection
0 to 9F
F: Through Mode
H1-15
Contact Input 15 Function Selection
0 to 9F
F: Through Mode
H1-16
Contact Input 16 Function Selection
0 to 9F
F: Through Mode
Setting
Function
Page
Setting
Function
Page
1
LOCAL/REMOTE Selection
31
PID Integral Hold
2
External Reference 1/2 Selection
32
Multi-Step Speed Reference 4
3
Multi-Step Speed Reference 1
33
Thermostatic Switch (N.C.)
4
Multi-Step Speed Reference 2
34
PID Soft Starter Cancel
5
Multi-Step Speed Reference 3
35
PID Input Level Selection
6
Jog Reference Selection
40
Forward Run Command (2-Wire Sequence)
7
Accel/Decel Time Selection 1
41
Reverse Run Command (2-Wire Sequence)
8
Baseblock Command (N.O.)
42
Run Command (2-Wire Sequence 2)
9
Baseblock Command (N.C.)
43
FWD/REV Command 2 (2-Wire Sequence 2)
A
Accel/Decel Ramp Hold
44
Add Offset Frequency 1
B
Drive Overheat Alarm (oH2)
45
Add Offset Frequency 2
C
Analog Terminal Input Selection
46
Add Offset Frequency 3
E
ASR Integral Reset
60
DC Injection Braking Command
F
Through Mode
61
External Search Command 1
10
Up Command
62
External Search Command 2
11
Down Command
63
Field Weakening
12
Forward Jog
67
Communications Test Mode
13
Reverse Jog
6A
Drive Enable
14
Fault Reset
70
Drive Enable 2
15
Fast Stop (N.O.)
71
Speed/Torque Control Switch
16
Motor 2 Selection
73
Door Switch NC
17
Fast Stop (N.C.)
75
Up 2 Command
18
Timer Function Input
76
Down 2 Command
19
PID Disable
77
ASR Gain Switch
MV1000ParameterGuide_E_conditional.book 171 ページ 2013年10月11日 金曜日 午後8時18分