2.7 H: Terminal Functions
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
199
n
H4-04, H4-14, H4-24, H4-34: Analog Output 1, 2, 3, 4 Cell Selection
Parameters H4-04, H4-14, H4-24, and H4-34 set the power cell numbers to be output from analog outputs 1 to 4. Their
settings are effective when 9
(power cell) has been set for H4-01, H4-11, H4-21 and H4-31 (Analog Output 1 to 4
Monitor Selections).
Figure 2.69
Figure 2.69 Analog Output Gain and Bias Setting
No.
Name
Setting Range
Default
H4-04
<1> The following table shows the power cell numbers to be output from analog outputs 1 to 4 depending on the settings.
Analog Output 1 Cell Selection
1 to 15
1
H4-14
Analog Output 2 Cell Selection
1
H4-24
Analog Output 3 Cell Selection
1
H4-34
Analog Output 4 Cell Selection
1
Setting
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Power cell No.
A1
B1
C1
A2
B2
C2
A3
B3
C3
A4
B4
C4
A5
B5
C5
Output Voltage
Output Voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Monitor Value
0%
H4-05, 15, 25, 35 = 0
H4-05, 15, 25, 35 = 1
10
V
-10 V
100%
5 V
15
V
-5 V
-15 V
-100%
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
Monitor Value
Monitor Value
0 V
3 V
10 V
100%
0%
Output Voltage
Output Voltage
H4-05, 15, 25, 35 = 0
H4-05, 15, 25, 35 = 1
10V
-10 V
100%
5 V
15 V
-5 V
-15 V
-100%
MV1000ParameterGuide_E_conditional.book 199 ページ 2013年10月11日 金曜日 午後8時18分