2.6 F: Option Settings
170
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
n
F6-06: Torque Reference / Torque Limit Selection from Comm. Option
Selects whether torque reference and torque limit values are assigned to the drive from the network.
Setting 0: Enabled
Setting 1: Disabled
n
F6-07: Multi-Step Speed Enable/Disable when NetRef/ComRef is Selected
Selects the treatment of multi-step speed inputs when the NetRef command is set.
Setting 0: Multi-step speed operation disabled
If the NetRef command is selected, multi-step speed input frequency references are disabled.
Setting 1: Multi-step speed operation enabled
Even if the NetRef command is selected, multi-step speed inputs are still active and can override the frequency reference
from the communications option.
n
F6-08: Reset Communication Parameters
Determines whether communication-related parameters (F6-
/F7-
) are reset when the drive is initialized using
parameter A1-03.
Setting 0: Do not reset parameters F6-
/F7-
when the drive is initialized with A1-03
Setting 1: Reset F6-
/F7-
when the drive is initialized with A1-03
Note:
F6-08 is not reset when the drive is initialized.
u
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set up the drive to operate on a PROFIBUS-DP network.
For details on parameter settings, refer to the Super Energy-Saving Medium-Voltage AC Drive FSDrive-MV1000 Option
PROFIBUS-DP Technical Manual.
u
DeviceNet Parameters
Parameters F6-50 through F6-63 set up the drive to operate on a DeviceNet network.
For details on parameter settings, refer to the Super Energy-Saving Medium-Voltage AC Drive FSDrive-MV1000 Option
DeviceNet Technical Manual.
u
Modbus TCP/IP Parameters
Parameters F7-01 through F7-16, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate on a Modbus TCP/
IP network.
For details on parameter settings, refer to the Super Energy-Saving Medium-Voltage AC Drive FSDrive-MV1000 Option
Modbus TCP/IP Technical Manual.
No.
Parameter Name
Setting Range
Default
F6-06
Torque Reference / Torque Limit Selection from Comm. Option
0, 1
0
No.
Parameter Name
Setting Range
Default
F6-07
NetRef/ComRef Function Selection
0, 1
0
No.
Parameter Name
Setting Range
Default
F6-08
Reset Communication Parameters
0, 1
0