2.7 H: Terminal Functions
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
183
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed (CLV) falls below the minimum output frequency set in
E1-09 or b2-01.
Note:
When using CLV control mode, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the
minimum output frequency set in E1-09.
Figure 2.52
Figure 2.52 Zero-Speed Time Chart
Setting 2: Speed Agree 1 (f
ref
/f
out
Agree 1)
Closes when the actual output frequency or motor speed (CLV) is within the Speed Agree Width (L4-02) of the current
frequency reference regardless of the direction.
Note: 1.
Detection works in both directions, forward and reverse.
2.
When using the CLV control mode, it is the motor speed
±
L4-02 that is considered.
Figure 2.53
Figure 2.53 Speed Agree 1 Time Chart
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 210
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01.
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01.
Status
Description
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference
±
L4-02.
OFF (open)
Output frequency
or
motor speed
Zero Speed
ON (closed)
E1-09 (Minimum Output Frequency) or
b2-01 (Zero Speed Level)
common_TMonly
L4-02
L4-02
Frequency
reference
Speed agree 1
ON
OFF
Output Frequency
or Motor Speed
MV1000ParameterGuide_E_conditional.book 183 ページ 2013年10月11日 金曜日 午後8時18分