1.3 Parameter Table
76
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u
U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
Page
U1: Operation Status Monitors
U1-01
(40H)
Frequency
Reference
Monitors the frequency reference. Display units are determined by o1-03.
10 V: Max
frequency
0.01 Hz
–
U1-02
(41H)
Output
Frequency
Displays the output frequency. Display units are determined by o1-03.
10 V: Max
frequency
0.01 Hz
–
U1-03
(42H)
Output Current
Displays the output current.
10 V: Drive
rated current
0.1 A
–
U1-04
(43H)
Control Method
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
No signal output
available
–
–
U1-05
(44H)
Motor Speed
Displays the motor speed feedback.
Display units are determined by o1-03.
10 V: Max
frequency
0.01 Hz
–
U1-06
(45H)
Output Voltage
Reference
Displays the output voltage.
10 V: Drive
rated voltage
1 V
–
U1-07
(46H)
DC Bus Voltage
Displays the average DC bus voltage of each Power Cell.
10 V: 2000 V
1 V
–
U1-08
(47H)
Output Power
Displays the output power (this value is calculated internally).
10 V: Drive
capacity (motor
rated capacity)
kW
1 kW
–
U1-09
(48H)
Torque
Reference
Monitors the internal torque reference.
10 V: Motor
rated torque
0.1%
–
U1-10
(49H)
Input Terminal
Status
Displays the input terminal status.
No signal output
available
–
–
U1-11
(4AH)
Output Terminal
Status
Displays the output terminal status
No signal output
available
–
–
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common
All Modes
common_
All Modes
common_
All Modes
common_
CLV
V/f
OLV
common
All Modes
common_
U1 - 10=
0 0 0 0 0 0 0 0
1: ON 0: OFF
Contact Input 2
Contact Input 3
Contact Input 4
Contact Input 5
Contact Input 6
Contact Input 7
Contact Input 8
All Modes
common_
U1 - 11=
0 0 0 0 0 0 0 0
1: ON 0: OFF
Contact Output 1
Contact Output 2
Contact Output 3
Contact Output 4
Contact Output 5
Contact Output 6
Contact Output 7
Contact Output 8
MV1000ParameterGuide_E_conditional.book 76 ページ 2013年10月11日 金曜日 午後8時18分