2.1 A: Initialization
98
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Note:
Parameter settings can be edited after entering the correct password. Performing a 2-wire initialization resets the password to
“0000”. Reenter the password in parameter A1-05 after drive initialization.
n
A1-06: Application Preset
Note:
This function is not available. Always set this parameter to its default setting “0 (disabled)”.
n
A1-90: Calendar Year
Sets the year for the calendar. The setting is used for recording event log data and trace data.
Note:
Some error arises, so periodic adjustment is recommended.
n
A1-91: Calendar Month and Day
Sets the month and day for the calendar. The setting records event log data and trace data.
Note:
Yaskawa recommends periodically checking this parameter, as the value may fluctuate over time.
n
A1-92: Calendar Hour and Minute
Sets the hour and minute for the calendar. The setting records event log data and trace data.
Note:
Yaskawa recommends periodically checking this parameter, as the value may fluctuate over time.
9
Press
or
to make sure that the settings can be changed.
10
Press
to cancel the changed settings.
11
The drive returns to the parameter display.
No.
Name
Setting Range
Default
A1-90
Calendar Year
2000 to 2099
2011
No.
Name
Setting Range
Default
A1-91
Calendar Month and Day
1.01 to 12.31
1.01
No.
Name
Setting Range
Default
A1-92
Calendar Hour and Minute
0.00 to 23.59
0.00
Step
Display/Result
←
→
-PRMSET-
V/F Control
“2”
PRG
Control Method
FWD
A1-02=
0
∗
2
∗
←
→
-PRMSET-
PRG
Control Method
FWD
A1-
02
= 2
∗
2
∗
Open Loop Vector