1.3 Parameter Table
56
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
H2-18
(3078H)
Alarm Output
Selection
Selects alarms to be output multi-functionally when the setting 21 (User-Set
Alarm) is set to H2-01 through H2-16.
Sets the value in hexadecimal so that the following Bit of an alarm to be
output is 1.
Bit 0: TMA1
Bit 1: TMA2
Bit 2: FAn
Default: 1
Min: 0
Max: FFFF
<45> The default setting for the drive with software versions S0107 and earlier is 3A.
<46> This parameter is available from the drive software versions S0108 and later.
H2 Contact Output Settings
H2-
Setting
Function
Description
Page
0
During Run
Closed: A Run command is active or voltage is output.
1
Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
2
Speed Agree 1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to
L4-02).
3
User-Set Speed Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
4
Frequency Detection 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
5
Frequency Detection 2
Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis
determined by L4-02.
6
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
7
DC Bus Undervoltage
Closed: DC bus voltage is below the Uv trip level set in L2-05.
8
During Baseblock (N.O.)
Closed: Drive has entered the baseblock state (no output voltage).
9
Frequency Reference Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
b1-15).
Closed: Digital operator supplies the frequency reference.
A
Run Command Source
Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.
B
Torque Detection 1 (N.O.)
Closed: An overtorque or undertorque situation has been detected.
C
Frequency Reference Loss
Closed: Analog frequency reference has been lost.
E
Fault
Closed: Fault occurred.
No.
(Addr.)
Name
Description
Setting
Page
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
common_
All Modes
All Modes
common_