2.7 H: Terminal Functions
182
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Table 2.27 Contact output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Figure 2.51
Figure 2.51 During Run Time Chart
Setting
Function
Page
Setting
Function
Page
0
During Run
1C
Motor 2 Selection
1
Zero Speed
1D
During Regeneration
2
Speed Agree 1
1E
Restart Enabled
3
User-Set Speed Agree 1
1F
Motor Overload Alarm (oL1)
4
Frequency Detection 1
20
IGBT Overheat Pre-Alarm (oH)
5
Frequency Detection 2
21
User-Set Alarm
6
Drive Ready
22
Mechanical Weakening Detection (N.O.)
7
DC Bus Undervoltage
2F
Maintenance Period
8
During Baseblock (N.O.)
30
During Torque Limit
9
Frequency Reference Source
31
During Speed Limit
A
Run Command Source
32
During Speed Limit in Torque Control
B
Torque Detection 1 (N.O.)
37
During Frequency Output
C
Frequency Reference Loss
38
Drive Enabled
E
Fault
39
Watt Hour Pulse Output
F
Through Mode
3A
Cooling Fan, Transformer Abnormal
Temperature Rise
10
Minor Fault
3C
LOCAL/REMOTE Status
11
Fault Reset Command Active
3D
During Speed Search
12
Timer Output
3E
PID Feedback Low
13
Speed Agree 2
3F
PID Feedback High
14
User-set Speed Agree 2
40
Close Command for Commercial Power Supply
Side Breaker
15
Frequency Detection 3
41
Close Command for Drive Secondary Side
Breaker
16
Frequency Detection 4
42
Completion Signal for Synchronous Transfer
17
Torque Detection 1 (N.C.)
4C
During Fast Stop
18
Torque Detection 2 (N.O.)
4D
oH Pre-Alarm Time Limit
19
Torque Detection 2 (N.C.)
60
Drive Cooling Fan Alarm
1A
During Reverse
62
Inrush Current Suppression Circuit Fault
1B
During Baseblock (N.C.)
100 to 160 Function 0 to 60 with Inverse Output
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
common_TMonly
MV1000ParameterGuide_E_conditional.book 182 ページ 2013年10月11日 金曜日 午後8時18分