1.3 Parameter Table
40
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
E2-08
(315H)
Motor Iron-Core
Saturation
Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux.
Automatically set during Auto-Tuning.
Default: 0.75
Min: E2-07
Max: 0.75
E2-09
(316H)
Motor Mechanical
Loss
Sets the motor mechanical loss as a percentage of motor rated power (W).
Adjust the setting in the following circumstances:
• When there is a large amount of torque loss due to motor bearing friction
• When there is a large amount of torque loss in a fan or pump application
Default: 0.0%
Min: 0.0%
Max: 10.0%
E2-10
(317H)
Motor Iron Loss for
Torque
Compensation
Sets the motor iron loss.
Default:
Min: 0 W
Max: 65535 W
E2-11
(318H)
Motor Rated Power Sets the motor rated capacity in kW (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Default:
Min: 0 kW
Max: 65000 kW
E3: V/f Pattern for Motor 2
E3-01
(319H)
Motor 2 Control
Mode Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 2
Min: 0
Max: 3
E3-04
(31AH)
Motor 2 Maximum
Output Frequency
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In
this case, the setting for E3-08 will be disregarded. Ensure that the four
frequencies are set according to these rules or an oPE10 fault will occur:
E3-04
≥
E3-06 > E3-07
≥
E3-09
Note:
E3-07 and E3-08 are only available in the following
control modes: V/f Control, Open Loop Vector.
Default:
Min: 40.0 Hz
Max: 120.0 Hz
E3-05
(31BH)
Motor 2 Maximum
Voltage
Default:
Min: 0.0 V
Max: 13000 V
E3-06
(31CH)
Motor 2 Base
Frequency
Default:
Min: 0 Hz
Max: 120 Hz
E3-07
(31DH)
Motor 2 Mid Output
Frequency
Default:
Min: 0.0 Hz
Max: 120.0 Hz
E3-08
(31EH)
Motor 2 Mid Output
Frequency Voltage
Default:
Min: 0 V
Max: 13000 V
E3-09
(31FH)
Motor 2 Minimum
Output Frequency
Default:
Min: 0.0 Hz
Max: 120.0 Hz
E3-10
(320H)
Motor 2 Minimum
Output Voltage
Default:
Min: 0 V
Max: 13000 V
E3-11
(345H)
Motor 2 Mid Output
Frequency 2
Default: 0.0
Min: 0.0 Hz
Max: 120.0 Hz
E3-12
(346H)
Motor 2 Mid Output
Frequency Voltage 2
Default: 0 V
Max: 0 V
Max: 13000 V
E3-13
(347H)
Motor 2 Base
Voltage
Default: 0 V
Max: 0 V
Max: 13000 V
E4: Motor 2 Parameters
E4-01
(321H)
Motor 2 Rated
Current
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Default:
Min: 10% of drive
rated current
Max: 200% of
drive rated current
E4-02
(322H)
Motor 2 Rated Slip
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Default:
Min: 0.00 Hz
Max: 20.00 Hz
No.
(Addr.)
Name
Description
Setting
Page
CLV
V/f
OLV
common
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
Output Voltage (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07 E3-06 E3-11 E3-04
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 40 ページ 2013年10月11日 金曜日 午後8時18分