2.4 d: Reference Settings
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
155
u
d7: Offset Frequency
n
d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using contact inputs
programmed for Offset frequency 1, 2, and 3 (H1-
= 44, 45, 46). The selected offset values are added together if
multiple inputs are closed simultaneously. The value is set as a percentage of the Maximum Output Frequency.
Note:
This function can be used to replace the “Trim Control” function (H1-
= 1C, 1D) of older Yaskawa drives.
illustrates the Offset frequency function.
Figure 2.41
Figure 2.41 Offset Frequency Operation
No.
Name
Setting Range
Default
d7-01
Offset Frequency 1
-100.0 to 100.0%
0.0%
d7-02
Offset Frequency 2
-100.0 to 100.0%
0.0%
d7-03
Offset Frequency 3
-100.0 to 100.0%
0.0%
Frequency
reference
Offset Frequency 1 [d7-01]
(Signed)
Offset Frequency 2 [d7-02]
(Signed)
Offset Frequency 3 [d7-03]
(Signed)
Contact input
(H1-
=44) = on (closed)
Contact input
(H1-
=45) = on (closed)
Contact input
(H1-
=46) = on (closed)
SFS
Frequency
reference after
soft starter
common_TMonly
MV1000ParameterGuide_E_conditional.book 155 ページ 2013年10月11日 金曜日 午後8時18分